Short Circuit Isolator |
Standard Features
• Can be placed at any location on SLC loop
• Checks the line for short circuit at power up; if the line is normal, the relay
will be returned on. If a line short is detected, the relay remains open
• Indication of short circuit by a yellow LED
Application
The AVENGER AS6003 Short Circuit Isolator provides the capability of allowing NFPA SLC
Style 7 installations
Technical Specifications |
| Absolute Maximum Applied Voltage | S, SC 41 VDC |
| Supply Voltage Nominal | S, SC 33 VDC |
| Normal Current Consumption | 270 μA |
| Average Current Consumption (Short Circuit Condition) | 10 mA |
| Visual Indicator (Yellow Status LED) | Normal Condition No indication Active (Short) Condition On Steady |
| SLC Maximum Resistance | 50 ohms |
| Weight | 1.4 oz |
| Maximum Humidity | up to 90%, non-condensing |
| UL Ambient Installation Temperature Range | 32º F to 120º F |
| Dimensions | 4.2” W x 4.7” H x 1.4” D |


There are no reviews yet.